Application
The circuit module KAL-S7 transmits the electric signal of the load cell to a Siemens S7
or a similar control device (PLC).
Function
The circuit module KAL_S7 receives the current signal from the load cell, amplifies it correspondingly to the range
of the load cell and supplies a tare signal with the result that the output signal of the circuit module is 4 mA (live zero) when the
container or tank on the load cell is empty.The output signal of the KAL-S7 is a regulated current signal between 4 and 20 mA, which
can be transmitted via an unshielded cable for a distance of more than 100 m. The maximum load resistance is 500 ohms. Therefore, the
circuit module supplies a maximum output voltage of 10 V for an output current of 20 mA. Input signal, output signal and the supply
voltage of the module are electrical isolated (3-way isolation).
Power supply for the module KAL-S7
The circuit module should be supplied with 24 V DC in the range of 20 to 30 V. Poor condenser smoothing is sufficient.
An important advantage is the comfortable possibility to adjust the tare simply with a screw button without needing to change
the programme of the S7 afterwards.
See also
datasheet Circuit Module KAL-S7 (Acrobat Reader, 38 KB).
|